151 Front Street Toronto Data Center
Open
Space for up to 800sqaure feet of cabinet space
Private
cages available
Top-quality, electrostatic dissipative raised floor tiles designed
for 175 psf, and in some facilities
300 lbs. psf, floor load
Meet all
code specifications for safety and electrical grounding, per NFPA 70
DC power
and communication cabling tray pathways
Optical
fiber guide conveyance system
Heavy load
freight elevators or loading dock access to the space
Comprehensive and flexible cabling infrastructure
Security & Access
24/7
security management via the Security Operations Center (SOC)
Remote
camera monitoring 24/7, backed by digital recordings on file for 30
days
Access to
equipment area 24/7 days via card key and pass code only
Escort
services 24/7 at sites with non-secured equipment areas
Locking
cabinets and/or cages
Full CCTV
surveillance
Power Infrastructure
200 watts
per square foot including HVAC
120/208V
AC and -48V DC available
Generator
capacity designed to multiple 1 to 2 Mg Watt generators
Size of
fuel tank 1,000 to 2,000 gallons
Generator
both auto start and auto transfer. Isolation bypass feature on
automatic transfer switch.
Minimum
24-hour run time fuel capacity.
Two-hour
response for fuel delivery
UPS backup
power
Voltage
output 480 transformed to 120/208 V
-48 Volt
DC Battery Plant
1200 amp
expandable to 10,000 amp
2-hour
battery reserve non-redundant, 4 hours redundant
"True"
A/B power feeds
Grounding
in accordance with NFPA 70
Environmental Controls
Under-floor cooling provided by computer-room grade equipment
Cooling
not less than 200 BTU/h per square foot with an N+1 redundancy
Temperature is maintained at 72 degrees F dry bulb at ASHRAE 1%
In the
event of a power interruption HVAC systems (and entire facility)
operate on diesel generators
30% to 60%
humidity non-condensing. Humidity control delivered through ATS/Liebert
units via
infra-red humidifier
Interconnection Options
Managed
Meet Me Room (MMR) to facilitate interconnection
Broad
choice of leading fiber and circuit carriers in each facility
Pre-run
conduit assures rapid connection to new carriers. Large number of
access providers in
Buildings assures the lowest possible
telecommunication link charges
Access
providers are encouraged to locate muxes within site to
facilitate interconnectivity
Overhead
cable trays are provided for connectivity
Layer 2
switching architecture for public interconnection and peering at
select locations
24x7
diagnostic remote switch fabric and port monitoring
Fire Detection & Suppression
Dry-pipe
pre-action sprinkler rated for telecommunication equipment/computer
room
Integrated
smoke/heat detector system
Under-floor leak
detection system |
1415 Bonhill Road Mississauga Data Center
6000
square feet of cabinets
Private
cages available
Mini Vaults up to
600square feet
Top-quality, electrostatic dissipative raised floor tiles designed
for 175 psf, and in some facilities
300 lbs. psf, floor load
Meet all
code specifications for safety and electrical grounding, per NFPA 70
Communication cabling tray pathways
Optical
fiber guide conveyance system
Loading
dock access to the space
Comprehensive and flexible cabling infrastructure
Security & Access
24/7
security management via the Security Operations Center (SOC)
Remote
camera monitoring 24/7, backed by digital recordings on file for 60
days
Access to
equipment area 24/7 days via card key only Escort services 24/7 at
sites with non-secured equipment areas
Locking
cabinets and/or cages
Full CCTV
surveillance
Power Infrastructure
200 watts
per square foot including HVAC
120/208V
AC available
100%
generator backup
Generator
capacity 400kw
Size of
fuel tank 1400 gallons
Generator
both auto start and auto transfer. Isolation bypass feature on
automatic transfer switch.
Minimum
24-hour run time fuel capacity.
Two-hour
response for fuel delivery
UPS backup
power provided by APC
Voltage
output 600 transformed to 120/208 V
400 amp
expandable to 1500 amp
2-hour
battery reserve non-redundant, 4 hours redundant
"True"
A/B/C power feeds
Grounding
in accordance with NFPA 70
Environmental Controls
Under-floor cooling provided by computer-room grade equipment
Cooling
not less than 200 BTU/h per square foot with an N+1 redundancy
Temperature is maintained at 72 degrees F dry bulb at ASHRAE 1%
In the
event of a power interruption HVAC systems (and entire facility)
operate on diesel generators
30% to 60%
humidity non-condensing. Humidity control delivered through ATS/Liebert
units via infra-red humidifier
Interconnection Options
Managed
Meet Me Room (MMR) to facilitate interconnection
Broad
choice of leading fiber and circuit carriers via 151 Front Stree
Backhaul
Pre-run
conduit assures rapid connection to new carriers. Large number of
access providers in buildings assures the lowest possible
telecommunication link charges
Overhead
cable trays are provided for connectivity
24x7
diagnostic remote switch fabric and port monitoring
Layer 2
switching architecture for public interconnection and peering at
select locations
24x7
diagnostic remote switch fabric and port monitoring
Fire Detection & Suppression
Dry-pipe
pre-action sprinkler rated for telecommunication equipment/computer
room
Integrated
smoke/heat detector system
Under-floor leak
detection system |